Category: PCB Spring Terminal Block
Item | Data | ||
APPROVAL | |||
Test standard | IEC/ EN60998-1:2004 / UL1059 | ||
Pitch [mm] | 7.50 | ||
Poles | 02-XXP | ||
EN60998 Test data | VDE certificate NO. 40022088 | ||
Rated voltage [V] | 450.00 | ||
Rated current [A] | 18.00 | ||
Rated connection capacity(solid/stranded) [mm2] | 2.50 | ||
Surge voltage category/pollution degree/material group | III/2/I | ||
Withstanding Voltage [KV/min] | 2.00 | ||
Rated torque [N.m] | 0.40 | ||
UL1059Test data | UL File Number E228872 | ||
Use group | B | C | D |
Rated voltage [V] | 300.00 | / | 300.00 |
Rated current [A] | 20.00 | / | 20.00 |
Rated connection capacity (solid/stranded) [AWG] | 44560.00 | ||
Rated torque [Lb. in] | 3.54 | ||
General data | / | ||
Screw | M2.5 | ||
Inflammability classUL94 | V-0 | ||
Ambient temperature [℃] | -40~+105 | ||
Relative humidity | 5%-95% | ||
Inspection standard | MIL-STD-105E II | ||
AQL | 0.65 | ||
Warranty | 12 months | ||
Material and plating | / | ||
Housing | PA66 | ||
Screws | Steel,Zn plated | ||
Contact | Copper alloy,Sn plated | ||
Cage | Copper alloy,Ni plated | ||
Wire connecting | |||
Recommended stripping length 6-7mm; | |||
For solid wire, stripping wire to the appointed length, then tightening with rated torque. | |||
For stranded wire: stripping wire to the appointed length, mating with corresponding type of ferrule, then tightening with rated torque. | |||
Tightening process should be steady, can’t use explosive force. |
Please Leave Your Product Enquiry Here. We will Get Back To You Soon.
Mobicon - Remote Electronic Sdn Bhd