Category: PCB Spring Terminal Block
Item | Data | ||
APPROVAL | |||
Test standard | IEC/ EN60998-1:2004 / UL1059 | ||
Pitch [mm] | 3.81 | ||
Poles | 01-XXP | ||
EN60998 Test data | VDE certificate NO. 40006127 | ||
Rated voltage [V] | 250 | ||
Rated current [A] | 10 | ||
Rated connection capacity(solid/stranded) [mm2] | 1.5 | ||
Surge voltage category/pollution degree/material group | III/2/I | ||
Withstanding Voltage [KV/min] | 2 | ||
Rated torque [N.m] | / | ||
UL1059Test data | UL File Number E228872 | ||
Use group | B | C | D |
Rated voltage [V] | 300 | / | 300 |
Rated current [A] | 5 | / | 5 |
Rated connection capacity (solid/stranded) [AWG] | 20-18 | ||
Rated torque [Lb. in] | / | ||
General data | / | ||
Screw | / | ||
Inflammability class UL94 | V0 | ||
Ambient temperature [℃] | -40~+105 | ||
Relative humidity | 5%-95% | ||
Inspection standard | MIL-STD-105E II | ||
AQL | 0.65 | ||
Warranty | 12 months | ||
Material and plating | / | ||
Housing | PA66 | ||
Spring | Stainless | ||
Pin header | Copper alloy,Sn plated | ||
Wire connecting | |||
9-10mm; Recommended stripping length 9-10mm; | |||
1.For solid wire, stripping wire to the appointed length ,press button and insert the wire. | |||
2.For stranded wire: stripping wire to the appointed length, mating with corresponding type of ferrule, then tightening with rated torque. |
Please Leave Your Product Enquiry Here. We will Get Back To You Soon.
Mobicon - Remote Electronic Pte Ltd